Hello,
I have tested this node with node-red with my raspberrypi and Siemens S7200 smart PLC
It supports variable like. Input (I0.0) , Output (Q0.0), Memory Variables MW, MB. and working well.
But not able to read & write Variable Memory VB, VW , Vbit, and timer e.g T100 , counters.
Please help to how to get control this variable with nodeS7.
The text was updated successfully, but these errors were encountered:
I don't have access to an S7-200 PLC with Ethernet so I have not been able to test any of these things. But I think you can access the V area using DB1.
So to access V0.0, use DB1,X0.0 and to access VW8 use DB1,INT8 - please let me know if this works for you, other data types should work as well.
S7-200 timers and counters have their own unique data type in the S7 protocol and support hasn't been added for those yet so this will not work. I would consider adding in the future if you would be able to test but hopefully the V area will get you going for now.
Hello,
I have tested this node with node-red with my raspberrypi and Siemens S7200 smart PLC
It supports variable like. Input (I0.0) , Output (Q0.0), Memory Variables MW, MB. and working well.
But not able to read & write Variable Memory VB, VW , Vbit, and timer e.g T100 , counters.
Please help to how to get control this variable with nodeS7.
The text was updated successfully, but these errors were encountered: